Short answer: Yes, but not for the entire network. Radio over Fiber (RoF) is being adopted primarily for in-building coverage and distributed antenna systems (DAS) rather than replacing outdoor macro networks (Not Yet…See my post about Photonic Networking). When combined with Passive Optical LAN (POLAN), RoF becomes even more powerful by leveraging the regional public safety network infrastructure—connecting schools and municipal buildings to Emergency Operations Centers (EOCs) distributed across public safety facilities like police stations, fire departments, and emergency management offices.


Why RoF is Being Adopted

Regulatory Mandates

Public safety codes are driving RoF adoption:

  • NFPA 72 and IFC Section 510 require reliable indoor coverage for first responders
  • Many jurisdictions now mandate 95% in-building coverage with minimum signal strength (-95 dBm for 700 MHz, -100 dBm for 800 MHz)
  • New construction and major renovations must demonstrate compliance before certificate of occupancy
  • Schools, hospitals, high-rises, and large commercial buildings face stricter requirements

Technical Advantages

  • Coverage Challenges: Traditional coaxial runs between donor antennas and bi-directional amplifiers (BDAs) suffer from high RF losses over long distances (6-7 dB per 100 feet).
  • RoF Advantage: Fiber links eliminate these losses, enabling long-distance connections between donor antennas, BDAs, and DAS headends without degrading signal quality. Fiber can run miles with negligible loss. This is critical in large campuses, high-rise buildings, and tunnels.

POLAN Integration for Geographically Separated Nodes

Schools and municipal buildings connect to the regional public safety network through EOCs distributed across public safety facilities (police stations, fire departments, emergency management offices). Using POLAN, the same fiber backbone that delivers IT services can also transport RF signals for public safety DAS:

  • Shared Fiber Infrastructure: POLAN uses single-mode fiber to connect remote Optical Network Terminals (ONTs) in buildings to an Optical Line Terminal (OLT) at the regional public safety facility.
  • RoF Overlay: RF signals for 700/800 MHz public safety bands can ride on dedicated wavelengths or separate fibers within the same cable plant. Think of it like different colors of light traveling through the same fiber—data uses one wavelength, voice uses another, and public safety radio uses a third, all without interfering with each other.
  • Power Integration: ONTs typically include PoE+ ports that can power DAS equipment, access points, and IoT sensors. With NEC 2026 updates for fault-managed power systems (Class 4 circuits), higher-power DAS components can be safely powered through the same low-voltage infrastructure.
  • Benefits: Reduced trenching costs, simplified maintenance, future-proof scalability for both IT and life-safety systems, and integration with the regional public safety network’s backup power infrastructure (located at distributed EOC nodes) ensures resilience during outages.

Understanding the Donor Antenna

A donor antenna is an outdoor antenna mounted at the regional public safety facility (EOC node) that receives public safety radio signals from external macro networks (700/800 MHz base stations) and “donates” them to the in-building DAS system. It also transmits signals from first responders inside buildings back to the external network, enabling two-way communication.

Signal Flow:

Regional PS Network → Donor Antenna (at EOC) → BDA/Headend → Fiber (RoF) → Remote DAS → Indoor Antennas → First Responder Radios

Key Advantage: By leveraging donor antennas at strategically positioned public safety facilities across the region, well-positioned antennas connected to the regional public safety network can serve multiple remote buildings via fiber. This eliminates the need for each school or municipal building to have its own donor antenna with line-of-sight to the macro network—a significant cost and complexity reduction.

Typical Architecture

[Regional PS Network]                 [School Campus]
   [EOC/PS Facility]                     Building A
      OLT                                  ONT → DAS
       |                                    |
       |--- Single Fiber (< 12 miles) ----  Building B
       |                                    ONT → DAS
       |                                    |
    Headend                                Building C
  (Donor Antenna)                         ONT → DAS

This single multi-strand fiber run connects remote sites to the regional public safety network while carrying both IT network traffic and public safety radio signals.


Cost-Benefit of POLAN + RoF

Factor Traditional LAN + DAS POLAN + RoF Hybrid
Cabling Multiple copper runs + coax Single fiber backbone
Telecom Closets Required per building/floor Minimal (ONT only)
Power & Cooling Distributed UPS for switches Centralized at OLT
Maintenance Multiple active devices Fewer points of failure
Scalability Limited by copper distance Fiber supports gigabit+
Integration Separate networks for IT & DAS Shared infrastructure

Bottom Line: POLAN reduces costs by:

  • Eliminating multiple telecom rooms and active switches
  • Lowering power and cooling requirements
  • Reducing trenching and conduit for separate networks
  • Providing a future-proof backbone for IT and public safety systems

Case Study: K-12 Campus Integration

Consider a typical school district with a 5-building campus located 12 miles from a regional public safety facility with an EOC node:

Traditional Approach:

  • 5 telecom rooms ($15K equipment each = $75K)
  • Separate DAS headend at school ($40K)
  • 5 UPS systems for switches ($3K each = $15K)
  • Annual cooling costs for 5 rooms (~$5K/year)
  • Total initial cost: ~$130K + ongoing OpEx

POLAN + RoF Approach:

  • Single OLT at regional public safety facility (shared with IT)
  • Connection to regional public safety network infrastructure
  • 5 ONTs at school buildings ($2K each = $10K)
  • Minimal telecom closets (ONT only, no active cooling)
  • RoF DAS integrated with existing fiber
  • Total initial cost: ~$50K + minimal OpEx

Net savings: $80K upfront + $5K annually in cooling/maintenance costs


Current Use Cases

  • In-Building Public Safety DAS: Vendors such as Honeywell and ADRF offer fiber-based DAS solutions for 700/800 MHz public safety bands. These systems are UL 2524 certified and comply with fire and building codes.
  • Campus Deployments: Schools and municipal buildings increasingly leverage POLAN for IT and DAS integration, reducing complexity and improving resilience.
  • Healthcare Facilities: Hospitals use RoF to maintain reliable emergency communications throughout complex, multi-building campuses with challenging RF environments.

  • Hybrid Architectures: Expect more integration of RoF in distributed public safety networks as agencies upgrade for interoperability and resilience.
  • Mission-Critical Fiber DAS: Fiber-based DAS is becoming the standard for new construction projects due to code compliance and performance benefits.
  • NEC 2026 Alignment: The consolidation of low-energy system requirements under NEC Chapter 7 and expanded provisions for fault-managed power systems (Class 4) simplify the electrical design for POLAN + RoF deployments, enabling higher power delivery to DAS equipment while maintaining safety standards.
  • Distributed Resilience: By locating OLTs at regional public safety facilities with backup generators and UPS systems, POLAN + RoF leverages existing emergency infrastructure to ensure public safety communications remain operational during power outages—when they’re needed most.
  • Not a Full Migration: Outdoor macro networks for 800 MHz public safety still rely on traditional RF infrastructure; RoF is mainly a transport layer for indoor and extended coverage scenarios.

For deeper understanding of RoF and POLAN integration in public safety contexts, consider exploring:

  • Architectural Design Patterns: Detailed fiber topology designs for school-to-emergency services connectivity, including redundancy and failover strategies
  • Performance Comparisons: Quantitative analysis of RoF versus traditional coaxial systems across cost, signal quality, and operational metrics
  • Compliance Frameworks: Comprehensive overview of NFPA 72, IFC 510, and UL 2524 testing requirements and certification processes
  • SMART Building Integration: How POLAN supports convergence of IT infrastructure, building automation, and life-safety systems (see reference 8 below)

References

  1. NFPA 72: National Fire Alarm and Signaling Code
  2. International Fire Code (IFC)
  3. UL 2524: Standard for In-Building 2-Way Emergency Radio Communication Enhancement Systems
  4. ADRF Technologies - Distributed Antenna Systems
  5. Honeywell Building Technologies - Emergency Communications
  6. CommScope - Passive Optical LAN Solutions
  7. Tellabs - Passive Optical LAN (POL) Technology
  8. SMART Building Certifications: A Technical and Programmatic Framework
  9. Photon Networks: Architectures, Applications, and Emerging Trends
    • Related post exploring photonic networking fundamentals and optical communications technologies
    • Photonic Networking